Used Vibration Analysis
 

 

Sponsored Advertisers:


Vibration Analyzer Accessories www.Portermax.com


Vibration Analyzer
Repair Service
www.tezzco.com


Vibration Training
www.4xdiagnostics.com



Need Training Or Technical Assistance For Vibration Analysis
   Technical Papers and Diagnostic Guides > AC Electric Motor Faults

AC Electric Motor Faults For Vibration Analysis Diagnostics

Alternating current (AC) induction motors operate by creating a rotating magnetic field from currents flowing throughout the stator windings. In the rotor assembly, this stator current induces current flow in the rotor bars.

If current is passed through a conductor positioned perpendicular to a magnetic field a force is produced. The direction of the force acts perpendicular to both the direction of the magnetic field and the current flowing through the conductors. This force will make the rotor rotate, effectively chasing the rotating magnetic field.

Alternating current (AC) induction motor windings are designed to create pairs of magnetic poles. Like pairs will repel each other when the magnetic fields line up pole to pole, while opposite pole pairs will attract each other. The electromagnet polarity will reverse as the AC power source continuously alternates the current through the coils. This changing pattern of polarity generates torque. The result is motor shaft mechanical rotation.

AC motor formulas

Motor Synchronous Speed (NSYNCH)

NSYNCH Pole Pairs
3600 2
NSYNCH = 120 x (Line Frequency, Hz 1800 4
# Poles 1200 6
900 8
NSYNCH = (7200, CPM) 720 10
# Poles 600 12

Slip Frequency (FSLIP)

FSLIP = (NSYNCH - Actual RPM)

Pole Passing Frequency (FPOLE)

FPOLE = (FSLIP x (# Poles))

Rotor Bar Passing Frequency

FRBPF = (RPM x (# of Rotor Bars))

Motor Waveform Vibration Frequancy

AC Motor Rotor Electrical Faults (Type I)

The AC motor rotor electrical faults is a result of broken or cracked rotor bars, rotor laminations or shorted end rings, or defective or loose rotor bar joints. These faults can also be traced to cast squirrel cage motors because of casting (porosity) problems.

These faults create a series of amplified 1x RPM harmonic peaks. The harmonics usually have low amplitude sidebands sets spaced at pole passing frequency. The normally present peak at 2x line frequency is either found at very low amplitudes or absent.

To resolve these closely spaced sidebands a high resolution spectrum is required. To detect this type of motor fault, the 24000 CPM spectrum with a 6400 FFT line resolution will also be used.

Severity is not usually judged by amplitudes levels, rather by the simple presence of the pole pass sidebands in the vibration spectrum. Deterioration over time is tended to be indicated by increased numbers of sideband sets. To confirm this fault and determine its cause, motor electrical testing (motor current testing) is recommended.

FSLIP = (NSYNCH - Actual RPM)
FPOLE = (FSLIP x (# of poles))

AC Motor Vibration Spectrum
A normal AC motor signature ought to include a rotor bar passing frequency (RBPF) response. This response takes place when each rotor bar passes slight disruptions within the magnetic field because of the electrical current’s path through the stator/rotor geometry. An elevated RBPF is created when the rotor bars pass a significant disruption in these fields produced when the current path is altered or distorted from broken or cracked rotor bars, loose or defective rotor bar joints, improperly brazed rotor bar joints, porous rotor bar castings, or electrical arcing across the rotor bar to end ring interfaces.

RBPF is recognized as an integer multiple of rotor speed, and will usually have sidebands spaced at 2x electrical line frequency (7200 CPM). Rotor eccentricity problems can be indicated by additional (less dominant) sidebands sets spaced at 1x RPM.

AC motor may have from 35-96 rotor bars, so an FFT spectrum with sufficient frequency range will be necessary to capture this fault. 1x and 2x RBPF will be captured by a 360000 CPM with a 1600 FFT line resolution, and will provide enough resolution to define the 2x LF sidebands.

Severity is usually judged by changes in RBPF amplitudes over time. Amplitude variation with load is common.

FRBPF = (RPM x (#of rotor bars))
Vibration Spectrum FFT AC Induction Motor